Bosch Climate 5000 Series Installation Manual page 22

Wall mounted ductless single split air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

2 2 | Bosch Climate 5000 Series Wall Mounted Ductless Single Split Air Conditioner / Heat Pump
5.
Clamp fl aring block on the end of the pipe. The end of the pipe must extend
beyond the edge of the fl are form in accordance with the dimensions shown
in the Table 6.
Figure 27
Piping extension beyond fl are form
Outer diameter
of tube mm (in.)
Ø 6.35 (Ø 0.25")
Ø 9.52 ( Ø 0.375")
Ø 12.7 ( Ø 0.5")
Ø 16 ( Ø 0.63")
Table 6
Flaring tool
Figure 28
6.
Place fl aring tool onto the fl aring block.
7.
Turn the handle of the fl aring tool clockwise until the pipe is fully fl ared.
8.
Remove the fl aring tool and fl aring block, then inspect the end of the pipe
for cracks and even fl aring. Slide the nut up to see if the fl are is of proper
diameter and does not interfere with the threads in the fl are nut.
Data subject to change
A mm (in.)
Min.
Max.
0.7 (0.0275")
1.3 (0.05")
1.0 (0.04")
1.6 (0.063")
1.0 (0.04")
1.8 (0.07")
2.0 (0.078")
2.2 (0.086")
A
Tube
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or to
deform the piping in any way. You should fi rst connect the low-pressure (suction)
pipe, then the high-pressure pipe (liquid line).
Minimum Bend Radius
When bending connective refrigerant piping, the minimum bending
radius is 10cm (4in). See Figure 29.
Radius
Figure 29
Installation Manual
≥10cm (4in)
03.2019 | Bosch Thermotechnology Corp.