Push button configuration (QSA2700)

4.4 Push button configuration (QSA2700)
4.4.1 On-event addressing (Climatix
Enter addressing mode and
configuration workflow via
push button
18 | 40
On-event addressing is a rapid configuration approach working together with
Siemens Climatix
controllers.
TM
The sensor is wired and connected to the Climatix
Press the
LED
button for
1...5 s
Constant red Press and hold the button
5...10 s
LED off
LED flashes
yellow for
0...30 s
controllers configuration)
TM
TM
Action
More details
Release the button
Entering the addressing mode, LED
flashes yellow for 30 s.
Communication is established
automatically when:
Then:
After a successful pairing, the LED
flashes green for 60 s, then turns to
permanent green.
Otherwise, the LED turns back to its
original state.
Short press the button to fix
If the LED is flashing, a short press of
the address to 246.
the push button fixes the address to
246.
The LED is off for 2 s, then turns
yellow for 2 s and then turns to
permanent green.
The address is 246.
Further configuration should be
carried out from controller side.
controller via Modbus.
Address is set to 246
temporarily.
Baud rate is 19200 (default).
Format is 1-8-E-1 (default).
Address is 246.
Master writes the Modbus
parameters.
Master writes "1" into register
4x0768 ("Bus configuration
command") to activate the
change.