Table X — 50HCQA04 Single Stage Cooling with Single Speed Indoor Fan Motor
VOLTAGE RANGE
V-Ph-Hz
MIN
208-1-60
187
230-1-60
187
208-3-60
187
230-3-60
187
460-3-60
414
575-3-60
518
Table Y — 50HCQA05 Single Stage Cooling with Single Speed Indoor Fan Motor
VOLTAGE RANGE
V-Ph-Hz
MIN
208-1-60
187
230-1-60
187
208-3-60
187
230-3-60
187
460-3-60
414
575-3-60
518
Table Z — 50HCQA06 Single Stage Cooling with Single Speed Indoor Fan Motor
VOLTAGE RANGE
V-Ph-Hz
MIN
208-1-60
187
230-1-60
187
208-3-60
187
230-3-60
187
460-3-60
414
575-3-60
518
APPENDIX D — ELECTRICAL INFORMATION
COMP (ea)
MAX
RLA
LRA
253
16.6
79
253
16.6
79
253
10.4
73
253
10.4
73
506
5.8
38
633
3.8
37
COMP (ea)
MAX
RLA
LRA
253
19.8
109
253
19.8
109
253
13.1
83
253
13.1
83
506
6.1
41
633
4.4
33
COMP (ea)
MAX
RLA
LRA
253
25.0
134
253
25.0
134
253
15.9
110
253
15.9
110
506
7.0
52
633
5.1
40
OFM (ea)
WATTS
FLA
190
1.0
190
1.0
190
1.0
190
1.0
190
0.5
190
0.5
OFM (ea)
WATTS
FLA
325
1.4
325
1.4
325
1.4
325
1.4
325
0.8
325
0.8
OFM (ea)
WATTS
FLA
325
1.4
325
1.4
325
1.4
325
1.4
325
0.8
325
0.8
54
IFM
EFF at
TYPE
Full Load
DD-STD
78%
DD-STD
78%
DD-STD
78%
MED
87%
HIGH
87%
DD-STD
78%
MED
87%
HIGH
87%
DD-STD
78%
MED
87%
HIGH
87%
DD-STD
78%
MED
72%
HIGH
78%
IFM
EFF at
TYPE
Full Load
DD-STD
78%
DD-STD
78%
DD-STD
78%
MED
87%
HIGH
69%
DD-STD
78%
MED
87%
HIGH
69%
DD-STD
78%
MED
87%
HIGH
69%
DD-STD
78%
MED
72%
HIGH
78%
IFM
EFF at
TYPE
Full Load
DD-STD
78%
DD-STD
78%
DD-STD
78%
MED
69%
HIGH
89%
DD-STD
78%
MED
69%
HIGH
89%
DD-STD
78%
MED
69%
HIGH
89%
DD-STD
78%
MED
78%
HIGH
77%
FLA
7.4
7.4
7.4
5.2
6.9
7.4
4.9
6.7
4.0
2.5
3.4
4.0
1.6
2.0
FLA
7.4
7.4
7.4
5.2
5.2
7.4
4.9
5.2
4.0
2.5
2.6
4.0
1.6
2.0
FLA
7.4
7.4
7.4
5.2
8.4
7.4
5.2
8.3
4.0
2.6
4.2
4.0
2.0
2.8