Puron ® (R-410A) Refrigerant; Refrigerant Charge - Carrier WeatherMaster 50HCQ04-12 Service And Maintenance Instructions

Single package rooftop heat pump/electric heat with puron (r-410a) refrigerant
Table of Contents

Advertisement

LPS/LOC
Filter
Drier
2B
1B
DFT 1
Acutrol
DFT 2
Outdoor Coil
5/8" HEX
®
PURON
(R-410A) REFRIGERANT
This unit is designed for use with Puron (R-410A) refrigerant.
Do not use any other refrigerant in this system.
Puron (R-410A) refrigerant is provided in pink (rose) colored
cylinders. These cylinders are available with and without dip
tubes; cylinders with dip tubes will have a label indicating this
feature. For a cylinder with a dip tube, place the cylinder in the
upright position (access valve at the top) when removing liquid
refrigerant for charging. For a cylinder without a dip tube, invert
the cylinder (access valve on the bottom) when removing liquid
refrigerant.
Because Puron (R-410A) refrigerant is a blend, it is strongly
recommended that refrigerant always be removed from the cyl-
inder as a liquid. Admit liquid refrigerant into the system in the
discharge line. If adding refrigerant into the suction line, use a
commercial metering/expansion device at the gage manifold;
Cooling Liquid Lines
1A
Comp 2
2A
Heating Mode Liquid Lines
Fig. 15 — Typical Unit Piping Schematic (50HCQ08, 09 Shown)
SEAT
1/2-20 UNF RH
0.596
30°
0.47
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 16 — CoreMax
Reversing
Valve
HPS
Reversing
HPS
Comp 1
Accuater
2C
(7.5 ton units only)
Accuater
1C
(7.5 ton units only)
CORE
(Part No. EC39EZ067)
WASHER
O-RING
1/2" HEX
1
Access Port Assembly
remove liquid from the cylinder, pass it through the metering
device at the gage set and then pass it into the suction line as a
vapor. Do not remove Puron (R-410A) refrigerant from the
cylinder as a vapor.

Refrigerant Charge

The amount of refrigerant charge is listed on the unit's name-
plate. Refer to Carrier GTAC2-5 Charging, Recovery, Recy-
cling and Reclamation training manual and the following pro-
cedures.
Unit panels must be in place when unit is operating during the
charging procedure. If unit is equipped with a head pressure
control device, bypass it to ensure full fan operation during
charging.
Charge checking and adjustments must be made while the sys-
tem is operating in Cooling only.
1. CoreMax is a registered trademark of Fastest, Inc.
11
2D
1D
Valve
Indoor Coil
Strainer
45°
DEPRESSOR PER AHRI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
TXV
TXV