Essential Steps during Engineering

2.3 Configuring the Relay Serial Data Communication

2.3
Configuring the Relay Serial Data Communication
You can configure the 7SR45 Argus relay by using the keys on the relay fascia. Scroll down from the SETTING
MODE and navigate to the COMMUNICATION menu and change the settings for the communication port if
needed.
Reydisp Evolution uses the IEC 60870-5-103 protocol to communicate.
When connecting the relay to a PC using the front USB port, the Reydisp Evolution automatically detects the
relay. If the USB-Protocol selected is IEC60870-5-103, then setting changes are not required.
Table 2-1
Description
COM1-RS485 Protocol
Selects protocol to use for COM1-
RS485
COM1-RS485 Stn Addr
Sets the station address for COM1-
RS485
COM1-RS485 Baud Rate
Sets the communications baud rate
for COM1-RS485
COM1-RS485 Parity
Selects whether parity information
is used
COM1-RS485 Mode
Selects whether the port is Local or
Remote.
COM2-USB Protocol
Selects protocol to use for COM2-
USB
COM2-USB Stn Addr
Sets the station address for COM2-
RS485
COM2-USB Mode
Selects whether the port is Local or
Remote.
20
Communication Settings
Range
OFF
IEC60870-5-103
MODBUS-RTU
0 to 254 for IEC60870-5-103
1 to 247 for MODBUS-RTU
1200
2400
4800
9600
19200
38400
57600
None
Odd
Even
Local
Local or Remote
Remote
OFF
IEC60870–5–103
MODBUS–RTU
0 to 254 for IEC60870–5–103
1 to 247 for MODBUS–RTU
Local
Local or Remote
Remote
Default
MODBUS-RTU
1
19200
None
Local or Remote
IEC60870–5–103
1
Local or Remote
Reyrolle, Engineering Guide, Manual
C53000-G7040-C102-1, Edition 08.2020