Fujitsu ASUG09LZAS Service Manual page 80

Wall mounted type, refrigerant r410a inverter, indoor/outdoor
Hide thumbs Also See for ASUG09LZAS:
Table of Contents

Advertisement

Check point 6. Check the remote controller
Hold down the THERMO SENSOR button until the thermo sensor icon is turned off.
→ If the space is still too warm, go to
Check point 7. Check function settings
Using the table on the right adjust function 31. (Room Temperature Control for indoor unit sensor)
NOTE: For details of function setting number 31, refer to
WORKING on page 05-1.
Check point 8. Check the remote controller display
Is the "Thermo Sensor Icon" displayed on the screen?
→ If no, go to
"Check point
Check point 9. Check the function Setting
Is function 48 (Room temperature sensor switching) set to 01?
→ If no, go to
"Check point
3-7. Too warm
"Check point
End
End
8-1".
9-1".
- (03-44) -
7".
"Function settings "
in Chapter 5. FIELD
3. Troubleshooting without error code