11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to
Function
Setting value
number
61
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to
Function
Setting value
number
62
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to
Function number
66
1-1. Function settings by using remote controller
"External heater output"
00
01
02
03
Auxiliary heater control by outdoor temperature 1
04
Auxiliary heater control by outdoor temperature 2
"External heater output"
Heater: On
00
-5.4 °F (-3 °C)
01
-3.6 °F (-2 °C)
02
-3.6 °F (-2 °C)
03
-5.4 °F (-3 °C)
04
-7.2 °F (-4 °C)
05
-9.0 °F (-5 °C)
"External heater output"
Setting value
00
01
02
03
04
05
06
07
08
on page 05-20.
Setting description
Auxiliary heater control 1
Auxiliary heater control 2
Heat pump prohibition control
on page 05-20.
Setting description
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
-1.8 °F (-1 °C)
on page 05-20.
Setting description
-4.0 °F (-20 °C)
-0.4 °F (-18 °C)
3.2 °F (-16 °C)
6.8 °F (-14 °C)
10.4 °F (-12 °C)
14.0°F (-10 °C)
17.6 °F (-8 °C)
21.2 °F (-6 °C)
24.8 °F (-4 °C)
- (05-7) -
Factory
setting
Factory
setting
Heater: Off
Factory setting
1. Function settings