Display Reference Table - Eaton ON-LINE Series Manual

Table of Contents

Advertisement

4.5

Display reference table

NO
Status
1
0~35% load capacity
2
36%~55%load capacity
Line
3
56%~75%load capacity
mode
4
76%~95%load capacity
5
96%~105%load capacity
6
0~20% battery capacity
7
21%~40% battery capacity
Battery
8
41%~60% battery capacity
mode
9
61%~80% battery capacity
10
81%~100% battery capacity
11
Bypass mode
12
Overload alarm
13
Overload in line mode, not transfer to
bypass mode
14
Overload in line mode, transfer to
bypass mode
15
Line abnormal
16
Bypass abnormal
17
Overload in battery mode, per-alarm
18
Overload in battery mode, cut off the
output
19
Over temperature
20
Inverter fault
21
Output short circuit fault
22
BUS voltage abnormal
23
BUS short circuit
24
Charger and battery damaged
25
Fans failure
26
Parallel operation fault
27
ID repeat
28
No battery
29
Battery voltage low
30
Battery over-charged
31
Reverse of Line and Neutral
32
Battery fault
1 #
2 #
3 #
4 #
5 #
38
LED
6 #
7 #
8 #
9 #
Alarm
10#
None
None
None
None
None
Once every 1s
Once every 4s
Once every 4s
Once every 4s
Once every 4s
Once every 2
mins
Twice every 1s
Twice every 1s
Twice every 1s
None
Once every 4s
Twice every 1s
Continuous beep
Continuous beep
Continuous beep
Continuous beep
Continuous beep
Continuous beep
Once every 1s
Once every 1s
Continuous beep
Continuous beep
Twice every 1s,
totally 6 times
Once every 1s
Continuous beep
Once every 2
mins
Continuous beep