Configuring the Low and
Low Low Alarms

The Low Alarm

5-8
To configure the XDP Low and Low Low alarms, access the setup
menu as described on page 5-4 and complete the following steps:
Range
Cal
Setup
4-20mA-Out
Alarms
Note: The other six alarm relays listed in the alarm setup menu are
discussed in the next section.
Alarms
Low-Alarm
Low-Low-Alarm
Normal-Alarm
Alarms Low-Alarm
Trip-Point
Test
Fail-Safe
At the next prompt, enter the percentage of hydrogen in air that
should trip the low alarm (typically 85.00%).
Alarms..Trip-Point
Trip-Point
xxx.xx
s
Alarms Low-Alarm
Trip-Point
Test
Fail-Safe
Use the [ ] and [ ] keys to
[Alarms]
select
and press
[ENTER]
.
Use the [ ] and [ ] keys to
[Low-Alarm]
select
and press
[ENTER]
.
Use the [ ] and [ ] keys to
[Trip-Point]
select
and press
[ENTER]
.
Use [ ] and [ ] to position the
cursor under the desired char-
acter. Then, use [ ] and [ ] to
increment the value. Press
[ENTER]
when done.
Use the [ ] and [ ] keys to
[Test]
[ENTER]
select
and press
Advanced Programming
.