Fig. 3-62 shows an example of installation.
Air-outlet grille

3-24. Installing the Drain Piping

(1) Prepare standard hard PVC pipe for the drain and
use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
When doing this, leave a gap between the drain
socket of the unit and the PVC pipe to allow the
drainage to be checked. The transparent drain
pipe allows you to check drainage. (Fig. 3-63)
CAUTION
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator
around the pipe, then secure it with the supplied
clamps. (Fig. 3-64)
NOTE
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
Panasonic̲PAC-i̲IndoorUnit̲US-le32   32
Panasonic̲PAC-i̲IndoorUnit̲US-le32   32
Air outlet duct
Ceiling material
Indoor unit
Fig. 3-62
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-63)
Bolt anchor
Suspension bolt
Air-intake grille
Transparent part for
checking drainage
Packing
Drain hose
(supplied)
(supplied)
Fig. 3-63
Clamps (supplied)
Drain insulator (supplied)
Fig. 3-64
32
Air-intake duct
Hose band
Adhere with
(supplied)
PVC adhesive.
Drain hose
Hard PVC pipe
adapter
(not supplied)
(supplied)