Features

The PC5720 is a fire module that can be used for ULC-listed non-residential fire applications. The
PC5720 can also be used as an interface between the control panel and either a serial printer or a
DVAC communications network.

Module Specifications

• 4-wire (QUAD) hook-up to the Keybus
• Current draw: 80mA standby; 100mA with printer, 120mA with F1/F2-L3
• Tamper and Trouble reporting codes
• Maximum cable length: 200 feet (61 meters)
• Eight zone inputs: one ground fault detection zone, two normally open Class A loops and five
standard Class B loops.

PC5720 connected to a serial printer

• True RS-232 technology
• DTR protocol
• Four possible baud rates: 300, 1200, 2400 or 4800

PC5720 connected to a DVACS network

• Automatic programming for extended DVACS reporting codes.
• Monitoring for DVACS line fault
• Module self diagnostics

Compatible Products

• PC5010
• PC5015