• Do not place heat sources.
• Be cautious not to generate a spark as follows:
– Do not remove the fuses with power on.
– Do not disconnect the power plug from the
wall outlet with power on.
– It is recommended to locate the outlet in a
high position. Place the cords so that they are
not tangled.
• If the indoor unit is not R-32 compatible, an error
signal appears and the unit will not operate.
• After installation, check for leakage. Toxic gas may
be generated and if it comes into contact with an
ignition source such as fan heater, stove, and cooker.
cylinders, make sure that only the refrigerant
recovery cylinders are used.
Preparation of fire extinguisher
• If a hot work is to be done, an appropriate fire
extinguishing equipment should have been
available.
• A dry powder or CO
fire extinguisher shall be
2
equipped near the charging area.
Ignition sources free
• Make sure to store the units in a place without
continuously operating ignition sources (for
example, open flames, an operating gas appliance
or an operating electric heater).
• The service engineers shall not use any ignition
sources with the risk of fire or explosion.
• Potential ignition sources shall be kept away from
the work area where the flammable refrigerant can
possibly be released to the surrounding.
• The work area should be checked to ensure that
there are no flammable hazards or ignition risks.
The "No Smoking" sign shall be attached.
• Under no circumstances shall potential sources of
ignition be used while in detection of leakage.
• Make sure that the seals or sealing materials have
not degraded.
• Safe parts are the ones with which the worker can
work in a flammable atmosphere. Other parts may
result in ignition due to leakage.
6 English
• Replace components only with parts specified by
Samsung. Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
Area ventilation
• Make sure that the work area is well ventilated
before performing a hot work.
• Ventilation shall be made even during the work.
• The ventilation should safely disperse any
released gases and preferably expel them into the
atmosphere.
• Ventilation shall be made even during the work.
Leakage detection methods
• The leakage detector shall be calibrated in a
refrigerant-free area.
• Make sure that the detector is not a potential
source of ignition.
• The leakage detector shall be set to the LFL (lower
flammability limit).
• The use of detergents containing chlorine shall be
avoided for cleaning because the chlorine may react
with the refrigerant and corrode the pipings.
• If leakage is suspected, naked flames shall be
removed.
• If a leakage is found while in brazing, the entire
refrigerant shall be recovered from the product or
isolated (e.g. using shut-off valves). It shall not be
directly released to the environment. Oxygen free
nitrogen (OFN) shall be used for purging the system
before and during the brazing process.
• The work area shall be checked with an appropriate
refrigerant detector before and during work.
• Ensure that the leakage detector is appropriate for
use with flammable refrigerants.
Labelling
• The parts shall be labelled to ensure that they have
been decommissioned and emptied of refrigerant.
• The labels shall be dated.
• Make sure that the labels are affixed on the system

Hide quick links: