Appliance Preparation; Gas Supply Connection; Convert To Left Side Gas Piping - Majestic fireplaces MO18 Installation Instructions Manual

Majestic burner/hearth and log kits for natural gas use only
Table of Contents

Advertisement

3

Appliance Preparation

Note: Have the gas supply line installed in accordance
with local building codes, if any. If not, follow ANSI 223.1.
Installation should be done by a qualified installer approved
and/or licensed as required by the locality. (In the Common-
wealth of Massachusetts installation must be performed by
a licensed plumber or gas fitter.)
A. Gas Supply Connection
Ensure fittings are of the appropriate size and type on the
gas line connection. If the tubing has to be cut to length be
sure to use the proper cutting and flaring tool. Also, be care-
ful not to crimp the tubing while bending. If the tubing be-
comes crimped, do not use for installation.
Certified joint compound or Teflon tape must be used on all
threaded male connections to ensure a tight seal.
WARNING
Gas Leak Risk
Support control when attaching pipe to
prevent bending gas line.
WARNING
Fire Risk
Explosion Risk
Personal Injury Risk
An explosion could occur if a connection is
made directly to an unregulated propane (LP)
tank.
Note: An individual manual shutoff valve (not supplied) is
required when installing this appliance. Check local codes
for location of shut off valve.
Note: A listed (and Commonwealth of Massachusetts
approved) 1/2 in. (13 mm) T-handle manual shut-off valve
and flexible gas connector are connected to the 1/2 in.
(13 mm) control valve inlet.
If substituting for these components, please consult
local codes for compliance.
B. Convert to Left Side Gas Piping
Remove the brass elbow from the right side.
Remove the cap from the left side.
Note: Prior to installing the fittings, use Teflon tape or joint
compound on the male threads.
Replace the cap on the opposite end of the burner tube.
Install the brass elbow on the left side of the burner.
20012914 7/05 Rev. 0
WARNING
Fire Risk
Explosion Risk
Verify inlet pressures.
H i g h p r e s s u r e m a y c a u s e o v e r f i r e
condition.
Low pressure may cause explosion.
Install regulator upstream of valve if line
pressure is greater than 1/2 psig.
WARNING
Fire Risk
Explosion Risk
Gas build-up during line purge may
ignite.
Purge should be performed by qualified
technician.
Ensure adequate ventilation.
Ensure there are no ignition sources such
as sparks or open flames.
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mo18mMo24m

Table of Contents