Fujitsu AS G07LUCA Series Service Instruction page 92

Universal floor/celling slim duct/mini duct compact cassette compact wall mounted/floor wall mounted type, inverter multi, refrigerant r410a, indoor/outdoor unit
Hide thumbs Also See for AS G07LUCA Series:
Table of Contents

Advertisement

Trouble shooting 32
OUTDOOR UNIT Error Method:
Discharge Pressure Sensor Error
Detective Actuators:
Discharge pressure sensor
Forecast of Cause:
1. Discharge pressure sensor connector disconnection, open
3. Main PCB failure
Test 1 : Check the discharge pressure sensor connection state
Connector connection state check
Cable open check
OK
Test 2 : Check the discharge pressure sensor
Sensor characteristics check
*For the characteristics of the discharge pressure sensor,
refer to the (SERVICE PARTS INFORMATION 4).
OK
Test 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN92:1-2) voltage value = 5V
Remove the
PRESSURE SENSOR
PRESSURE SENSOR
RED
1
1
WHITE
2 2
CN92
BLACK
3 3
Discharge pressure sensor (CN92:1-2)
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
Indicate of Display:
Indoor Unit
Operation lamp : 8 time Flash
Timer lamp          : 6 time Flash
ERROR CODE : [E : 86]
Detective details:
When any of the following conditions is satisfied, a discharge pressure
sensor error is generated.
30 seconds or more have elapsed since the outdoor unit power was
turned on and pressure sensor detected value < 0.3V continued
for 30 seconds or more
30 seconds or more have elapsed since the outdoor unit power was
turned on and pressure sensor detected value > 5.0V was detected.
from Main PCB, check the voltage.
PS
Outdoor Unit
. 2
i D
c s
h
DC
02-47
Monitor
A
B
C
D
E
8
6
: Light ON
: Light OFF
n : n time blinking
=
a
g r
e
p
e r
s s
u
e r
s
e
n
s
r o
a f
u l i
F
e r