4. LOUVER CONTROL

For Compact Wall Mounted Type, Wall Mounted Type < AS*G18 /24LFC* >
1. VERTICAL LOUVER CONTROL
(Function Range)
Each time the button is pressed, the air direction range
will change as follow:
Cooling / Heating / Dry mode / Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode : Horizontal flow
Heating mode
When the temperature of the air being blown out is low at the start of heating operation or during
defrosting, the airflow direction temporarily becomes
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range (
) for long period of time, since water vapor many condense near the outlet louvers and
drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow
Direction Louvers are left in the heating range for around 30 minutes, they will automatically
return to position
.
2. HORIZONTAL LOUVER CONTROL ( For
(Function Range)
Each time the button is pressed, the air direction
range will change as follows.
Cooling / Heating / Dry / Fan mode
3. SWING OPERATION
Vertical Airflow Swing Operation
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
Cooling / Dry / Fan mode(
Heating / Fan mode(
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted
and it stops at either upper end or bottom end.
Horizontal Airflow Swing Operation ( For AS
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
(Swinging Range)
Cooling / Heating / Dry / Fan mode :
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted
and it stops at either upper end or bottom end.
Vertical and Horizontal Airflow Swing Operation
When the horizontal swing signal is input from remote control, the combination of the vertical
and horizontal swing operation is performed.
Power Diffuser doesn't swing in any swing operation.
<Compact Wall Mounted Type>
: Downward flow
AS
ASU7/9/12RLF changes by manual.
) :
1
1
3
4
*
)
: AS
G07/09/12 [
4
6
*
1
5
(Fig.7 : Virtical Air Direction Range)
Vertical Louver
Vertical Louver
*
*
G07/09/12:
, AS
G18/24:
to prevent cold air being blown onto the body.
AS*G18/24LFC* )
(Fig.8 : Horizontal Air Direction Range)
Horizontal Louver
*
4
6
], AS
G18/24 [
G18/24 )
01-12
<Wall Mounted Type>
Power Diffuser
1
2
3
6
]
5
3
4