5. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
The Table 5 shows the fan speed of the outdoor unit.
( Table 5 : Fan speed of the outdoor unit )
AO*G36LBLA5
AO*G45LBLA6
7. COMPRESSOR CONTROL
6. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 6 .
( Table 6 : Compressor operation frequency range )
AO*G36LBLA5
AO*G45LBLA6
2. OPERATION FREQUENCY CONTROL AT START UP
2.
The compressor frequency soon after the start-up is controlled as shown in the Fig. 12 .
( Fig. 12 : Compressor control at Start-up )
H rps
G rps
E,F rps
C,D rps
B rps
A rps
G
H
[ Frequency ]
AO*G36LBLA5
AO*G45LBLA6
[ Time ]
AO*G36LBLA5
AO*G45LBLA6
Cooling
890/ 830/ 710/ 640/ 580/ 520/
460/ 390/ 340/ 290 rpm
Cooling
Min
Max
20
100
I
J
K
A rps
B rps
C rps
30
30
47
G ~ H
H ~ I
I ~ J
60sec
60sec
480sec
910/ 830/ 710/ 640/ 580/ 520/
460/ 390/ 340/ 290 rpm
Heating
Min
Max
20
100
L
M
N
D rps
E rps
47
60
J ~ K
K ~ L
120sec
300sec
01-19
Heating
O
F rps
G rps
60
80
L ~ M
M ~ N
N ~ O
180sec
120sec
120sec
H rps
100