4. After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be
saved when entire segments blinks and tracking mode begins.
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
CAUTION
❋ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
❋ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting
mode.
- If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored setting
is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be
saved.
Option
Input unit
Channel address
Main
Base heater
Main
Operation mode
Main
Snow accumulation
Main
prevention control
Silent mode
Main
Energy saving
Main
mode
SEG1
SEG2
SEG3
0
0
0
1
0
2
0
3
0
4
0
5
ENGLISH-45
SEG4
A
U
0
0
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0
2
0
3
0
4
0
0
0
1
Function of the option
Automatic address setting (default)
Manual address setting (0 to 15)
Enabled (default)
Disabled
Heat Pump (default)
Heating Only
Disabled (default)
Enabled
Manual Silent mode (-3 dB)
Manual Silent mode * 0.9 (-5 dB)
Manual Silent mode * 0.75 (-7 dB)
Manual Silent mode (-3 dB)
Low-noise Silent mode (default)
Disabled (default)
Enabled