Connection diagram of the RMIO board in the line-side converter

Internal connections to the RMIO board for the ACS800 IGBT Supply Control
Program are shown below. Do not change the connections.
Terminal block size:
2
cables 0.3 to 3.3 mm
(22 to 12 AWG)
Tightening torque:
·
0.2 to 0.4 N
m (0.2 to 0.3 lbf·ft)
1)
non-programmable I/O
2)
External earth (ground) fault
indication via digital input DI4: See
parameter 30.04 EXT EARTH FAULT.
3)
External alarm/fault indication via
digital input DI5: See parameter 30.05
EXT EVENT.
4)
START command via digital input
DI7: See parameter 16.01 RUN BIT
SEL.
X20
1
VREF-
Reference voltage -10 VDC,
1 kohm < R
2
GND
X21
1
VREF+
Reference voltage 10 VDC,
1 kohm < R
2
GND
3
AI1+
By default, not in use. 0(2)...10 V,
R
> 200 kohm
4
AI1-
in
5
AI2+
By default, not in use. 0(4)...20 mA,
R
= 100 ohm
6
AI2-
in
7
AI3+
By default, not in use. 0(4)...20 mA,
R
= 100 ohm
8
AI3-
in
9
AO1+
By default, not in use. 0(4)...20 mA,
R
< 700 ohm
10
AO1-
L
11
AO2+
By default, not in use. 0(4)...20 mA,
R
< 700 ohm
12
AO2-
L
X22
1
DI1
Acknowledgement of converter fan
2
DI2
Stop/Start
3
DI3
Acknowledgement from main contactor
4
DI4
By default not in use.
5
DI5
By default not in use.
6
DI6
By default not in use.
7
+24V
+24 VDC max. 100 mA
8
+24V
9
DGND
Digital ground
10
DGND
Digital ground
11
DI7(DIIL) By default not in use.
X23
1
+24V
Auxiliary voltage output and input, non-
isolated, 24 VDC 250 mA
2
GND
X25
1
RO11
Relay output 1: By default not in
use.
2
RO12
3
RO13
X26
1
RO21
Relay output 2: By default not in
use.
2
RO22
3
RO23
X27
1
RO31
Relay output 3: Main contactor
control
2
RO32
3
RO33
+ 24 VDC
-
Operation principle and hardware description
< 10 kohm
L
< 10 kohm
L
1)
2)
3)
4)
1)
35
1)