Daikin EWAP 800-C18AJYNN Installation, Operation And Maintenance Manual page 16

Air cooled screw chillers
Table of Contents

Advertisement

Electrical data EWAP-AJYNN/A R-407C
Unit size
Standard voltage (1)
Nominal unit current (2)
Max compressor current (3)
Fans current
Max unit current (3)
Max unit inrush current (4)
Max unit current for wires sizing (5)
Unit size
Standard voltage (1)
Nominal unit current (2)
Max compressor current (3)
Fans current
Max unit current (3)
Max unit inrush current (4)
Max unit current for wires sizing (5)
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 ° C entering/leav ing evaporator water temperature and 35° C ambient t emp.
(3)
Maximum current are based on: 14/9 ° C entering/leav ing evaporator water temperature and 46° C ambient t emp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.
(5) Compressor FLA + fans current.
D - KIMAC00512-09EN - 16/40
850
900
A
477
523
A
596
655
A
64
68
660
723
A
A
1051
1055
684
744
A
C13
C14
A
756
796
A
948
1002
A
100
104
A
1048
1106
A
1232
1332
A
1086
1146
950
C10
C11
400 V – 3f – 50 Hz
652
707
757
710
777
840
72
76
80
782
853
920
1125
1129
1172
804
864
924
C15
C16
C17
972
1023
1078
1056
1123
1184
112
112
112
1168
1235
1296
1406
1407
1486
1210
1266
1322
C12
710
888
96
984
1259
1026
C18
1121
1245
120
1365
1489
1386