General Data - SMA SUNNY TRIPOWER 15000TL Economic Excellence Installation Manual

Pv
Hide thumbs Also See for SUNNY TRIPOWER 15000TL Economic Excellence:
Table of Contents

Advertisement

Technical Data
Efficiency
Maximum efficiency, η
European weighted efficiency, η
13.2 General Data
Width x height x depth,
with handle of DC switch-disconnector*
Weight
Length x width x height of packaging
Transport weight
Climatic class as per IEC 60721-3-4
Environment category
Degree of pollution outside the enclosure
Degree of pollution inside the enclosure
Operating temperature range
Maximum permissible value for relative humidity,
non-condensing
Maximum operating altitude above MSL
Noise emission (typical)
Power loss in night mode
Topology
Cooling concept
Fan connection
Degree of protection as per IEC 60529
Protection class according to IEC 62103
Strain relief category of the cable glands
according to EN 50262
Grid Configuration
Approvals, as per 03/2013**
*Optional
** EN 50438: Does not apply to all country standard deviations of EN 50438
IEC 62109-2: In order to meet the requirements of this standard, the inverter must either be equipped with a multi-function relay
used as a fault indication relay or there must be a connection to Sunny Portal with the fault alarm in Sunny Portal activated.
RD 1699 and RD 661/2007: Contact the SMA Service Line for restrictions in specific regions.
NRS 97-1-2: This standard stipulates that a special label be attached to the AC distribution board to draw attention to the AC-side
disconnection of the inverter in the event of grid failure (for more details, see NRS 97-1-2, Sec. 4.2.7.1 and 4.2.7.2)
82
STP15-20TLEE-IA-en-23
max
EU
98.5%
98.2%
665 mm x 680 mm x 265 mm
780 mm x 380 mm x 790 mm
Outdoors
‒25°C to +60°C
3,000 m
≤ 51 dB(A)
< 1 W
Transformerless
OptiCool: temperature-controlled fan
Designed for safe disconnection in accordance
with DIN EN 62109-1
TN-C system, TN-S system, TN-C-S system,
TT grounding system
VDE-AR-N4105, VDE 0126-1-1, AS4777,
C10/11, PPDS, UTE C15-712-1, PPC,
EN50438, RD661/2007, IEC 61727, G59/2,
CEI 0-21, NRS 97-1-2, BDEW 2008,
RD1699:2011, NEN EN 50438,
DIN EN 62109-1, IEC 62109-2, SI4777
SMA Solar Technology AG
45 kg
53 kg
4K4H
3
2
100%
IP65
I
A
Installation Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents