Start Up

Seasonal Startup

When heating system is to be started for first time in the
season:
1. Disconnect electrical power.
2. If the heat exchanger does not have a p-trap and
condensate drain line, connect a hose to the drain
valve and drain any accumulated condensate.
3. Check all electrical terminals for tight connections.
4. Open all manual gas valves and ensure that these
valves operate freely.
5. Check the air shutter and modulating gas valve
linkages for tightness.
6. Clean dust, dirt, and debris from the air shutters on the
combustion fan and the air inlet louver.
7. Check the exhaust flue for debris and clean as
necessary.
8. Re-connect the power and initiate the startup
sequence.