First Start-up
If necessary, carry out
parameter reset to
factory setting
Parameterizing by
download or with
parameter modules
Function test
Further start-up and parameterization according to
4-2
If the PMU does not show status °005 after completion
of the unit initialization, or if the unit has already been
parameterized before, you should carry out a parameter
reset to factory setting.
AAA
After checking the unit and the cabling once more, power
up the line voltage and perform a function test according
to your parameterization.
WARNING
It must be ensured that no danger for
persons and equipment can occur by
energizing the power and the unit. It is
recommended not to couple the driven
machine until the function test has
been successfully completed.
your specific requirements
6SE7087-6KP50
Operating Instructions
SIMOVERT MASTERDRIVES
02.2005
See section
"Parameterization"
See section
"Parameterization"
siehe
"Anschließen"
und "EMV-
gerechter
Aufbau"