Fujitsu AB F18LAT Series Service Instruction page 47

Split type, room air, conditioner, floor ceiling type, duct type, cassette type models indoor unit outdoor unit inverter
Hide thumbs Also See for AB F18LAT Series:
Table of Contents

Advertisement

Trouble shooting 13
OUTDOOR UNIT Error Method:
Compressor Temperature Sensor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Compressor Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Rough value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
3 2 1
3 2 1
CN70
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Detective details:
0°C
5°C
10°C
169
130
101
70°C
80°C
90°C
8.70
6.27
4.60
2 1
2 1
4 3 2 1
2 1
2 1
4 3 2 1
CN72
CN73
CN71
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
ERROR CODE : E : 15
When Compressor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
15°C
20°C
30°C
79.1
62.6
40.0
100°C
120°C
140°C
3.43
2.00
1.22
02-16
40°C
50°C
60°C
12.3
26.3
17.8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents