( For AU Type )
Trouble shooting 6
INDOOR UNIT Error Method:
Water Drain Abnormal
Detective Actuators:
Indoor Unit Controller PCB Circuit
Float Switch
Forecast of Cause :
1. Float Switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is detective, replace it.
OK
OK
Check Point 2 :
Check Point 2 : Check Connector (CN9) / Wire
Check loose contact of CN9 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
OK
OK
Check Point 3 : Replace Controller PCB
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Indicate or Display:
Indoor Unit
: No LED
Outdoor Unit : No indication
ERROR CODE : E : 09
Detective details:
When Float Switch is ON for more than 3 minutes.
02-09
ON
ON
OFF