Electrical Box
Step
16 Remove the harness
from the right wire
saddle.
17
Disconnect the
connector [S80].
18
Pull out the clamp.
19 Disconnect the relay
connector for the
compressor.
20 Pull out the clamp from
the partition plate.
12
Procedure
Right wire saddle
[S80]
Clamp
Points
(R24304)
[S80]: four way valve coil
The cooling only models do
not have the harness for
[S80].
When reassembling, insert
the clamps of harnesses as
shown below.
[S40] [S80]
(R24305)
When reassembling,
connect the connectors in
the following order:
(1) [S80]
(2) [S20]
(3) [S40]
(4) [S70]
(R14312)
(R24306)
Si001163EA
[S20]
(R14363)
Removal Procedure