Note On Adding Refrigerant; How To Use App - Kaisai KRX-09AEXI Owner's Manual

Table of Contents

Advertisement

Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 7.5m (25').
In other areas, the standard pipe length is 5m (16'). The refrigerant should be charged from the service
port on the outdoor unit's low pressure valve. The additional refrigerant to be charged can be
calculated using the following formula:
e
Connective Pipe
Length (m)
< Standard pipe length Vacuum Pump
> Standard pipe
length
For R290 refrigerant unit, the total amount of refrigerant to be charged is no more than:
387g(<=9000Btu/h), 447g(>9000Btu/h and <=12000Btu/h), 547g(>12000Btu/h and <=18000Btu/h),
632g(>18000Btu/h and <=24000Btu/h).
CAUTION
l
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Air Purging
Method
Liquid Side: Ø 6.35 (ø 0.25")
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 0.13oZ/ft
Vacuum Pump
(Pipe length – standard length) x 10g/m
(Pipe length – standard length) x 0.10oZ/ft
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
(Pipe length – standard length) x 20g/m
(Pipe length – standard length) x 0.21oZ/ft
DO NOT
mix refrigerant types.
Additional Refrigerant
N/A
R32:
(Pipe length – standard length) x 24g/m
(Pipe length – standard length) x 0.26oZ/ft
R290:
(Pipe length – standard length) x 18g/m
(Pipe length – standard length) x 0.19oZ/ft
R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
R22:
(Pipe length – standard length) x 40g/m
(Pipe length – standard length) x 0.42oZ/ft
91
Liquid Side: Ø 9.52 (ø 0.375")
R32:
R290:
R410A:
R22:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents