Unpacking And Inspecting The Switch - Cisco Nexus 9332C Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Unpacking and Inspecting the Switch

Unpacking and Inspecting the Switch

Before you install the switch, be sure to unpack and inspect the switch for damage or missing components.
If anything is missing or damaged, contact your customer service representative immediately.
Tip
Keep the shipping container in case the chassis requires shipping at a later time.
Before you begin
Before you unpack the switch and before you handle any switch components, be sure that you are wearing a
grounded electrostatic discharge (ESD) strap. To ground the strap, attach it directly to an earth ground or to
a grounded rack or grounded chassis (there must be a metal-to-metal connection to the earth ground).
Step 1
Compare the shipment to the equipment list provided by your customer service representative and verify that you have
received all items, including the following:
• Accessory Kit
Step 2
Check for damage and report any discrepancies or damage to your customer service representative. Have the following
information ready:
• Invoice number of shipper (see packing slip)
• Model and serial number of the damaged unit
• Description of damage
Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide
16
Warning
Statement 1005 Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent)
protection. Ensure that the protective devices is rated not greater than 20A (North
America), 16A (Europe), and 13A (UK).
Note
For DC input application, please refer to the statement below:
Warning
Statement 1005 Circuit Breaker
This product relies on the building's installation for short-circuit (overcurrent)
protection. Ensure that the protective devices is rated not greater than 40A for
the regular DC power supplies (rated 48-60VDC) and 10A for the HVDC power
supplies.
Installing the Switch Chassis