INSTALLATION GUIDE
4
DIP Switch Configuration
ON
1 2 3 4 5 6 7 8
Select Network Type
Select Air
Conditioer Type
ON
1 2 3 4
5 6 7 8
*LGAP: LG Air conditioner Protocol
Multi V & Multi(LGAP applied) products
Configuration Methods
' 1 ON, All others OFF : Multi V products(Except CRUN
ON
products) or Multi(Non-Inverter) Product applied
1 2 3 4 5 6 7 8
Common PCB(Refer to NOTE) or Multi(Inverter)
Product + Central Controller(All types) - Without LGAP
' 1 and 4 ON, All others OFF : Multi V products(Except
ON
CRUN products) or Multi(Non-Inverter) Product
1 2 3 4 5 6 7 8
applied Common PCB or Multi(Inverter) Product +
Central Controller(All types) - Using LGAP
' 2 ON, All others OFF : Multi(Non-Inverter)
ON
Product + Centroller(All types) - Without LGAP
1 2 3 4 5 6 7 8
' 2 and 4 ON, All others OFF : Multi Non-
ON
Inverter Product
1 2 3 4 5 6 7 8
+ Central Controller(All Types) - Using LGAP
ON
' 1,2,3,4 ON : Multi V CRUN Product
+ Central Controller(All types) - Using LGAP
1 2 3 4 5 6 7 8
* Please refer the corresponding Central Controller
installation manual if you want to know whether your
Central Controller is compatible with LGAP or not.
CAUTION
Select Advanced Control Type
!
NOTE
Multi(Non-Inverter) Product applied
Common PCB
PCB P/NO. : 6871A20917*
P/NO. : 6871A20918*
P/NO. : 6871A20910*
Advanced Lock Control Type
- To use the advanced lock function (Run
Mode lock, Fan Speed lock,
Temperature Lock, and Temperature Range
lock; adjustable only within certain boundary)
by central controller, Set up the fifth dip
switch according to the type of outdoor prod-
uct.
- In case of advanced lock function, it can use
only the central controller applied to LGAP.
' 1, 4 and 5 ON, All others OFF :
ON
MultiV Products (Except CRUN
1 2 3 4 5 6 7 8
products) or MPS Inverter
Product + Central Controller
(All types) - Using LGAP
' 2, 4 and 5 ON, All others OFF :
ON
Multi Standard Product +
1 2 3 4 5 6 7 8
Central Controller (All types) -
Using LGAP
' 1, 2, 3, 4and 5 ON, All others
ON
OFF : MultiV CRUN Product +
1 2 3 4 5 6 7 8
Central Controller (All types) -
Using LGAP
!
NOTE
The advanced lock setting.
Some products do not support advanced lock
function.
In this case, The fifth dip switch on PI485 must
be on.
In case of product applied to advanced function, it
can process the advanced lock function without
fifth dip switch ON.
If all units support advanced lock function, It is
recommended that the fifth dip switch be off, so
that advanced lock function is processed faster.