Table ED-1 — Unit Wiring
Unit
Model No.
WSC060AD
WSC060AT
WSC072AD
WSC072AT
WSC090AD
WSC090AT
WSC120AD
WSC120AT
Notes:
1. All units to be installed under local codes.
PKGP-PRC004-EN
Electrical
Data
Standard Indoor Fan Motor
Unit
Minimum
Operating
Circuit
Voltage Range
Ampacity
342-456
18.9
180-220
37.2
342-456
21.9
180-220
38.4
342-456
24.8
180-220
47.6
342-456
31.2
180-220
59.5
Oversize Indoor Fan Motor
Maximum Fuse
Minimum
Size Or Maximum
Circuit
Circuit Breaker
1
Ampacity
25
18.9
50
37.2
30
22.9
60
43.9
35
26.5
60
50.2
40
31.2
60
59.5
Maximum Fuse
Size Or Maximum
Circuit Breaker
1
25
50
30
60
35
60
40
60
35