Table E3: WPHF Electrical Performance (Standard Static Blower Option-continued)
Blower Motor
Model No.
Volts/Hz/Ph
WPHF057
208/60/1
WPHF057
230/60/1
WPHF057
208/60/3
WPHF057
230/60/3
WPHF057
460/60/3
Table E4: WPHF Electrical Performance (High Static Blower Option)
Blower Motor
Model No.
Volts/Hz/Ph
WPHF047
208/60/1
WPHF047
230/60/1
WPHF047
208/60/3
WPHF047
230/60/3
WPHF047
460/60/3
WPHF057
208/60/1
WPHF057
230/60/1
WPHF057
208/60/3
WPHF057
230/60/3
WPHF057
460/60/3
24
Electrical
Requirements
Blower Motor
Compr.
HP
FLA
RLA
1/2
4.1
22.3
1/2
4.1
22.3
1/2
4.1
14.4
1/2
4.1
14.4
1/2
1.8
7.1
Blower Motor
Compr.
HP
FLA
RLA
1/2
4.6
14.6
1/2
4.6
14.6
1/2
4.6
10.6
1/2
4.6
10.6
1/2
2.2
4.2
1/2
4.6
22.3
1/2
4.6
22.3
1/2
4.6
14.4
1/2
4.6
14.4
1/2
2.2
7.1
Compr.
Compr.
Minimum Cir-
MCC
LRA
cuit Amps
34.8
122
32.0
34.8
122
32.0
25.5
101
22.1
25.5
101
22.1
11.1
51
10.7
Compr.
Compr.
Minimum Cir-
MCC
LRA
cuit Amps
22.8
92
22.9
22.8
92
22.9
16.5
101
17.9
16.5
101
17.9
6.6
51
7.5
34.8
122
32.5
34.8
122
32.5
22.5
101
22.6
22.5
101
22.6
11.1
51
11.1
UL Max Fuse
CSA
CASE
or HACR
Max. Fuse
Max.
Size
Circuit Brkr
50
60
50
50
60
50
35
50
45
35
50
45
15
20
20
UL Max Fuse
CSA
CASE
or HACR
Max. Fuse
Max.
Size
Circuit Brkr
35
50
40
35
50
40
25
50
45
25
50
45
15
25
20
50
60
50
50
60
50
35
50
45
35
50
45
15
25
20