RT-PRC016-EN
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.

Low Ambient Cooling

The Precedent
line features, with
ReliaTel
microprocessor controls, low
ambient cooling down to 18°C (0°F).
Contact your local Trane Representative
for more assistance with low ambient
cooling applications.
Barometric Relief
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option.
This accessory consists of gravity
dampers which open with increased
pressure. As the building air pressure
increases, the pressure in the unit return
air section also increases, opening the
dampers and relieving the conditioned
space.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZA-
TION.

Condensate Trap

The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.

Clearance Requirements

The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the local Trane sales personnel.
Unit Pitch
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where
condensate drain is connected.