Trane TSC060-120 User Manual page 21

Packaged cooling with electric heat rooftop units 50 hz
Table of Contents

Advertisement

Table PD-8 — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (SI)
25
50
3
m
/h
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
3260
-
-
-
3670
-
-
548
0.26
4080
-
-
584
0.33
4490
569
0.35
621
0.42
4890
612
0.45
660
0.51
External Static Pressure (Pascals)
275
300
CFM
RPM
kW
RPM
kW
1.12 Nom kW Std Motor
& Drive
3260
925
0.71
960
0.77
3670
944
0.81
978
0.87
4080
964
0.91
998
0.99
4490
986
1.04
1019
1.11
4890
1011
1.18
1043
1.26
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Table PD-8a — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (IP)
.10
.20
CFM
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1920
-
-
-
2160
-
-
548
0.35
2400
-
-
584
0.45
2640
569
0.47
621
0.56
2880
612
0.60
660
0.69
External Static Pressure (Inches of Water)
1.10
1.20
CFM
RPM
BHP
RPM
BHP
1-1/2 HP Standard Mtr
& Drive
1920
925
0.95
960
1.03
2160
944
1.08
978
1.17
2400
964
1.22
998
1.32
2640
986
1.39
1019
1.49
2880
1011
1.58
1043
1.69
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
RT-PRC016-EN
Performance
Data
75
100
RPM
kW
RPM
kW
-
573
0.25
630
0.30
602
0.31
656
0.37
635
0.38
682
0.45
670
0.47
715
0.54
706
0.58
749
0.64
325
350
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor
& Hi Static Drive
994
0.83
1026
0.89
1010
0.94
1043
1.01
1030
1.06
1063
1.14
1051
1.19
1082
1.27
1073
1.34
1103
1.42
1.50 Nom kW Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
.30
.40
RPM
BHP
RPM
BHP
-
573
0.34
630
0.41
602
0.42
656
0.50
635
0.52
682
0.60
670
0.64
715
0.72
706
0.78
749
0.86
1.30
1.40
RPM
BHP
RPM
BHP
994
1.11
1026
1.19
1010
1.26
1043
1.36
1030
1.42
1063
1.53
1051
1.60
1082
1.71
1073
1.79
1103
1.90
2 HP Over-Sized Mtr & Hi Static Drive
External Static Pressure (Pascals)
125
150
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Drive
680
0.36
726
0.41
706
0.43
751
0.49
732
0.51
777
0.58
758
0.60
802
0.68
789
0.71
830
0.79
375
RPM
kW
1057
0.95
1073
1.08
1092
1.21
1112
1.35
1133
1.51
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
.50
.60
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Drive
680
0.48
726
0.55
706
0.58
751
0.65
732
0.69
777
0.77
758
0.81
802
0.91
789
0.96
830
1.06
1.50
RPM
BHP
1057
1.27
← ← ← ← ←
1-1/2 HP Standard Motor &
1073
1.44
Hi Static Drive
1092
1.63
1112
1.81
1133
2.02
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
175
200
225
RPM
kW
RPM
kW
RPM
769
0.47
811
0.52
851
792
0.55
832
0.61
871
818
0.64
856
0.71
893
845
0.75
883
0.82
919
870
0.87
909
0.95
945
1.12 Nom kW Standard Motor
& Hi Static Drive
.70
.80
.90
RPM
BHP
RPM
BHP
RPM BHP
769
0.62
811
0.70
851
792
0.73
832
0.81
871
818
0.86
856
0.95
893
845
1.01
883
1.10
919
870
1.16
909
1.27
945
1-1/2 HP Standard Motor
& Hi Static Drive
250
kW
RPM
kW
0.58
889
0.65
0.67
908
0.74
0.77
930
0.84
0.89
953
0.96
1.02
979
1.10
1.00
RPM BHP
0.78
889
0.87
0.90
908
0.99
1.04
930
1.13
1.20
953
1.29
1.37
979
1.48
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents