Specification - Wolf FWS-2-60L Manual

Freshwater module, circulation module
Hide thumbs Also See for FWS-2-60L:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 14
Weight
Connections
Main components
DHW output
Min. permiss. operating temp.
Max. permiss. operating temp.
Max. permiss. operating pressure
Pump specification
22

Specification

8
approx. 21 kg
A = cold water IN, 1" female thread
B = DHW OUT, 1" female thread
C = from buffer, 1" male thread
D = to buffer, 1" male thread
E = DHW circulation line (not part of the standard delivery)
1 = thermostatic head
2 = power connection box
3 = plate heat exchanger
4 = flow switch
5 = HE charging pump
6 = indirect coil sensor
7 = push-in connection for DHW circulation unit (incl. dummy cap)
8 = DHW circulation unit (optional)
10 l/min at 50°C buffer temperature
2 °C
95 °C
DHW 10 bar heating water 3 bar
Primary pump:
230 V/50 Hz
Speed = 800 - 4660 rpm
Power consumption: 3 - 45 W
Rated current = 0.03 - 0.44 A
DHW circulation pump (optional):
230 V/50 Hz
Power consumption: 7.5 W (+ timer 1.5 W)
B
4
E
5
6
7
C
A
D
1
2
3