Data Setting Screens (Cont'd)
the following screens show the setting procedure for setting the data variables. they are accessed from
the main Data Setting screens (see
to begin: Set
or
battery teSt
inhibit
Voltage aDJ: +5
to aCCept: Set
Voltage aDJ: +4
to aCCept: Set
Voltage aDJ: -5
to aCCept: Set
loops through
eleven possibilities
Clear timer Set
to aCCept: Set
DeFaUlt SettingS
to aCCept: Set
38
page
33) when the SHIFT/SELECT key is pressed:
Shift
Set
battery teSt
+
Select
monitor
executes battery test and returns
to Data Setting screens
Shift
Set
Voltage aDJ: +5
+
to Change:SeleCt
monitor
Select
Shift
Set
Voltage aDJ: +4
+
to Change:SeleCt
Select
monitor
Shift
Set
Voltage aDJ: -5
+
to Change:SeleCt
Select
monitor
returns to Data Setting screens
(with new value applied)
Shift
Set
Clear timer Set
+
to Change:SeleCt
Select
monitor
executes battery test and returns
to Data Setting screens
Set
Shift
DeFaUlt SettingS
+
to Change:SeleCt
monitor
Select
executes battery test and returns
to Data Setting screens
this parameter has no options to set.
a battery test will be performed once
###%
the ShiFt + Set button is pressed.
if the bat teSt inhibit message is
displayed, it indicates that a battery
test has been performed recently.
the UpS will not allow frequent bat-
tery tests to insure that the batteries
remain in a fully charged state.
this parameter allows the user to off-
set the output voltage (while the unit
is running on-lline) in 1% increments
over a range of +/-5% total offset.
Default value is 0%
this parameter has no options to set.
pressing the ShiFt + Set button
while this message is displayed will
cancel timer settings.
this parameter has no options to
set. pressing the ShiFt + Set but-
ton while this message is displayed
will reset all variables to their default
value.
1600ep Series instruction manual