Important Safety Instructions; Qualified Personnel Only - Toshiba 1600EP Series Instruction Manual

Single phase - 3.6-rohs/3.6/6/8/10/14/18/22
Hide thumbs Also See for 1600EP Series:
Table of Contents

Advertisement

IMPORTANT SAFETY INSTRUCTIONS

this manual contains important instructions that should be followed during the installation and maintenance
of the UpS and its batteries.
hardwire-type UpS units are not equipped with an over-current protection device nor an output disconnect
for the aC output. a circuit breaker should be provided by the user between the UpS output and the load
input. this device should be rated as follows:
3.6RoHS kVA
240VAC
RATING
20 a
the nominal battery voltages for these models are as follows:
3.6RoHS kVA
BATTERY
VOLTAGE
144 Vdc
Servicing of the batteries should only be performed by a qualified factory authorized representative who
is knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries. to arrange for battery replacement, contact your nearest factory authorized service center.
1.
turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment ow
when performing maintenance.
2.
hardwire type UpS units are not equipped with an over-current protection device, nor do they have
an output disconnect for the aC output. therefore, a user-installed circuit breaker should be provided
between the UpS output and the load input.
3.
the maximum ambient operating temperature is 104 °F (40 °C).
4.
Battery servicing should be performed by qualified Toshiba representative only.
5.
Unauthorized personnel should not service batteries.
6.
Contact your toshiba authorized service center for battery replacement.

QUALIFIED PERSONNEL ONLY

Qualified personnel is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and has received safety training on the hazards
involved (refer to the latest edition of nFpa 70e for additional safety requirements).
Qualified personnel shall:
1.
have read the entire operation manual.
2.
be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and
equipment, and clear faults in accordance with established safety practices.
3.
be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
4.
Be trained in rendering first aid.
5.
be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.
1600ep Series instruction manual
3.6 kVA
6 kVA
20 a
30 a
3.6 kVA
6 kVA
216 Vdc
216 Vdc
288 Vdc
8 kVA
10 kVA
14 kVA
40 a
60 a
80 a
8 kVA
10 kVA
14 kVA
288 Vdc
288 Vdc
18 kVA
22 kVA
125 a
150 a
18 kVA
22 kVA
288 Vdc
288 Vdc
3