Toshiba 1600EP Series Instruction Manual page 24

Single phase - 3.6-rohs/3.6/6/8/10/14/18/22
Hide thumbs Also See for 1600EP Series:
Table of Contents

Advertisement

STANdArd MOdeLS: 3.6kVA-RoHS; 3.6kVA; 6kVA; 8kVA (CONT'D)
Unit (Capacity)
environment
operating temperature
59 – 77 °F (15 – 25 °C)
recommended
Storage temperature
installation area
operating humidity
altitude
acoustical noise
heat generation
operation Diagnosis
battery Check
input oV protection
battery lifetime
internal temperature
event Data Storage
applications
Switches
bypass Switch
bypass Disable
automatic retransfer
User interface
real time Clock
Schedule operation
rUn/Stop Disable
autostart
remote on/oFF
leD Display
lCD Screen
UpS operation: 6 Keys
buzzer Volume
power Connections
emergency power off
remote Contacts
rS232 aSCii interface
1.
Input/output figures rated for 240 volts. Output ratings given for 0.85PF are only valid when the input voltage is
greater than 204 volts; otherwise, ratings given for 0.70pF are applicable.
2.
at 6600 ft (2000 m) above sea level, output capacity should be derated by 3%
16
3.6 kVa-rohS
3.6 kVa (3.1 kw)
(3.1 kw)
1
60 hz
32 – 104 °F (0 – 40 °C)
to be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
< 3300 ft. (1000 m) above sea level
50 db (a) maximum @ 1 meter from front panel
1588 btU/hr
1588 btU/hr
Performed on start up, by schedule, on-demand (user configurable)
UpS calculates battery replacement time
based upon battery ambient temperature (lCD display, leD and beeps)
UpS gives indication of internal temperature, alarm when high temp
64 – Supply mode, 32 – backup, 16 – Faults
Static switch < ¼ cycle (50 hz – 5 ms/60 hz – 4.16 ms)
Factory or authorized service center selectable only
provided – Can be disabled from front panel
Standard – minimum 3 days memory backup during power loss
Schedule on/oFF operation of UpS using communication software
UpS has option for UpS to start automatically when aC is applied
Standard – external terminal
4 leD's indicating input/output condition, warning and battery operation
run/Stop, Set/monitor, Shift/Select, Del/page Down, reset/page Up
Selectable by keypad – low, high, mute
Standard – terminal contacts only
Standard (inV, byp, batt, lb, aC, Flt)
6 kVa (5.1 kw)
1
-4 – 104 °F (-20 – 40 °C)
30 – 90% non-condensing
2610 btU/hr
Standard
generator compatibility
16 characters x 2 lines
Standard – hard wire
Standard
1600ep Series instruction manual
8 kVa (6.8 kw)
1
1
50 hz
32 – 91 °F (0 – 33 °C)
2
3482 btU/hr