Carrier AquaSnap 30RB Series Installation, Operation And Maintenance Instructions page 41

Air-cooled liquid chillers
Table of Contents

Advertisement

30RB 432-522 - total heat reclaim condenser option
4" Victaulic type 75
6" Victaulic type 75
6" Victaulic
type 75
legend:
all dimensions are in mm.
Clearances required for maintenance and air flow
Clearances recommended for evaporator tube removal
Clearances recommended for heat exchanger removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
11.2.3 - Condenser water connection
4" Victaulic
type 75
Power connection
ATTENTION: The Victaulic flange sleeves of the conden-
ser are not installed, but supplied with the unit. The
temperature sensors and the condenser flow switch are in
the control box and wired. After connecting the Victaulic
flange sleeves, the temperature sensors must be installed,
as well as the water flow switch which must be located in
the condenser outlet.
NOTE: Non-contractual drawings.
When designing an installation, refer to the certified
dimensional drawings, available on request.
for the positioning of the fixing points, weight distribu-
tion and centre of gravity coordinates.
legend
1
Control valve
2
Air vent
3
Flow switch for the condenser (supplied)
4
Flexible connection
5
Condenser
6
Temperature sensor (supplied)
7
Drain
8
Buffer tank (if needed)
9
Filter (mesh size: 1.2 mm = 20 mesh)
10 Expansion tank
11 Fill valve
For user control connection
Size 522
41