Reports
To access Alarms, press the Alarms button in the lower left
corner of the screen. If the Alarm tab is not blinking red,
there are no alarms present.
Figure 45. Alarms tab

Compressor Alarms

If there is a compressor alarm, it will need to be manually
reset after it is resolved. Each compressor needs to be
reset manually:
1. Press Reports at the bottom of the display.
2. Press Unit Setup.
3. In the Setup report, locate the appropriate point. Use
the arrows to scroll through the report if needed.
4. Select the specific compressor.
5. Change the value from Normal to Reset.
6. Press Save. The point will automatically revert to its
default setting (Off).

Fan Alarms

If there is a fan alarm, it will need to be manually reset after
it is resolved. There is one fan reset for the entire wall fan.
1. Press Reports at the bottom of the display.
2. Press Unit Setup.
3. In the Setup report, press Supply Fan Failure Reset.
Use the arrows to scroll through the report if needed.
4. Press Reset.
5. Press Save.
6. When you want the fan to be available, press the
Release Override button in the top left.

General Alarms

General alarms are alarms that are not tied to fans or
compressors. They require a manual reset, and there is
one alarm reset for these alarms.
To reset a general alarm:
1. Press Reports at the bottom of the display.
2. Press Unit Setup.
3. In the Setup report, press Alarm Reset. Use the
arrows to scroll through the report if needed.
4. Press Reset.
5. Press Save.
PKG-SVX027A-EN

Water Purge

NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could
result in scaling, erosion, corrosion, algae or slime.
Use the services of a qualified water treatment
specialist to determine what water treatment, if any, is
required. Trane assumes no responsibility for
equipment failures which result from untreated or
improperly treated water, or saline or brackish water.
During the unoccupied mode, water-cooled units will
periodically circulate water through the condensers and
waterside economizer if the user has enabled the purge
function at the HI. The water purge function circulates
water to introduce fresh water-treatment chemicals and
help prevent water stagnation. The number of hours
between each periodic purge, or purge duration, is user-
defined at the HI between 1-999 hours. If the periodic purge
timer expires while the unit is in occupied mode, it will wait
for the next available unoccupied time before initiating
water purge.
Contrary, if a request for cooling occurs during a purge
sequence, purge will terminate and cooling will
commence.