Refrigerant Pipe Connections & Electrical Wiring Inlets
Line Voltage Inlets
7/8 in. (22 mm)
Liquid line connection
to outdoor unit
field-provided
swage connection
Ø 3/8 (10 mm)
NOTE - A maximum of (4) 12-AWG cabling can be used per 7/8" electrical inlet port. A maximum of (18) communica-
tion cables can be used per 1 1/8" electrical port.
NOTE - High Voltage Cabling and Low Voltage Communication Cabling shall not pass/occupy the same electrical
port. All VRF/Furnace Communication cabling must be 18 Gauge shielded/stranded.
NOTE - Suitable electrical connectors can be used to secure field wiring.
Figure 5. Refrigerant Piping Connections & Electrical Wiring Inlets

Before Installation

Select Air Handler Unit and AHU Control Kit Model

Verify the cooling capacity, internal volume and air
flow requirements of each 3rd party indoor unit using
Table 2.
Select the AHU Control kit model(s) by the indoor unit
capacity shown in Table 2.
Failure to adhere to these specifications can cause
performance degradation.
BOTTOM VIEW
Throttling devices (TXV, orifice, piston and cap tube,
etc.) in the indoor unit shall be removed, additional
modifications may be needed. Only Lennox VRF
wired local controller V0STAT51P-3 is allowed with
the AHU Control Kit. Two typical application layouts
are shown in Figure 1 and Figure 2.
Designs with these kits require approval by the
Lennox VRF Applications Team prior to installation.
7
Low Voltage Inlets
1-1/8 in. (29 mm)
Liquid line connection
to indoor unit
field-provided
swage connection
Ø 3/8 (10 mm)