ADC HiGain HMS-318 List 3 User Manual page 39

Higain managed shelf 19-inch, 3190 mechanic, 22-slot managed co shelf
Hide thumbs Also See for HiGain HMS-318 List 3:
Table of Contents

Advertisement

December 20, 2004
Power and Frame Ground Procedure
To avoid voltage differences from building up between the shelf ground (GND) bus and the
IMPORTANT
ground pins of the management terminal that connects to the RS-232 ports, connect the shelf
!
ground pins and the terminal ground bus to the TB1 FGND (frame ground) pin.
Step
1
Use locally approved practices to connect #12 AWG (minimum) power wiring from -48Vdc Office Battery
to -48VA and -48VB terminals on TB1-1 and TB1-2 (see <Cross-Ref>Figure 2).
2
Connect #12 AWG (minimum) power wiring from the Battery Returns to BAT RTN terminals on TB1-3
and TB1-4 (see <Cross-Ref>Figure 2).
Note:
Slots 1 through 11 on the HMS-318 List 3 shelf are powered by the -48VA bus. Slots 12 through 22
are powered by the -48VB bus.
In the HMU/HLU configuration, the HMU-319 is diode-OR'ed to both power busses to guard against power
failure in the event that one power supply is lost. This feature requires the two ground (GND) terminals to
be connected on the HMU card.
Alarms Procedure
Note:
As described in "Power and Alarm Connections" on page 7, the HMS-318 List 3 shelf provides alarm
outputs in the form of an Alarms wire-wrap field. This field consists of a three-pin wire-wrap header for alarm
management. Before connecting the alarm inputs, you must first determine whether the external alarm
equipment requires either an NO or an NC circuit to pass an alarm.
Step
1
Use locally approved practices to connect the alarm inputs to the Alarms wire-wrap field (see
on page
2-12).
Note:
The HMU-319 is required for NO and NC alarm operation.
LTPH-UM-1261-01
Action
1
2
-48VA
-48VB
FUSE
FUSE
15A MAX 15A MAX
Figure 2-2. Input Power Terminal Block (TB1)
Action
3
4
5
TB1
BAT
RTN
FGND
Chapter 2: Installation
Figure 2-3
2-11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Higain ltph-um-1261-01Higain t1mf2s04ra

Table of Contents