Alarm Management; Auto Reset Alarms; Manual Reset Alarms - Siemens POLYCOOL RWR470.10 Basic Documentation

Table of Contents

Advertisement

Notes
Siemens Building Technologies
HVAC Products
8

Alarm Management

Alarms in PolyCool470.10 are divided into two groups: auto reset alarms and manual
reset alarms.
• For an auto reset alarm, users are not required to acknowledge and reset it. The
corresponding device will be automatically restarted once the alarm status
disappears.
• Once a manual reset alarm is detected, the system will be stopped. Users need
acknowledge and reset it, and also manually restart the corresponding device after
the fault status is cleared.
When an alarm is detected, the corresponding device icon (if any) and the
continuously flash. An alarm code will be displayed on the screen.
• If more than one alarm is detected, the alarm codes will be displayed successively on
the LCD screen until the alarm status disappears, or until they are manually
acknowledged or reset (only for manual reset alarms).
• If the system detects warnings and alarms at the same time, the warning codes will
NOT be displayed on the LCD.
• The latest 20 normal alarms and manual reset alarms generated in total are
separately kept under the auto reset alarm (AR) and manual reset alarm (MR)
categories in the
menu.

Auto Reset Alarms

The following are codes for auto reset alarms with their meanings.
Codes
Meaning
AL01
Compressor low pressure (DI2)
AL02
Compressor high pressure (DI3)
AL03
Low inside supply water temperature protection (when less than AL01 in cooling mode)
AL04
Low outside supply water temperature protection (when less than AL01 in heating mode)
AL05
Inside supply temperature is over the high limit in heating mode(when over than AL03 in
heating mode)

Manual Reset Alarms

The following are codes for manual reset alarms with their meanings.
Codes
Meaning
AL11
Inside return temperature sensor(X1)
AL12
Inside supply temperature sensor(X2)
AL13
Outside temperature sensor(X3)
AL14
Domestic hot water temperature sensor(X4)
AL15
Outside supply temperature sensor(X5)
AL16
Outside return temperature sensor(X6)
AL17
Flow switch alarm after the
AL18
Alarm number of compressor low pressure within 24 hours is over the
AL19
Alarm number of compressor high pressure within 24 hours is over the
AL20
Low evaporator temperature
SIEMENS Controller
delay(AL05)
protection(AL08)
icon will
limit(AL06)
limit(AL07)
15/28
HEAT PUMP controller
27.11.2006