Cleaning Heating Surfaces (Gas Condensing Module); Checking Condensate Drain And Cleaning The Trap (Gas Condensing Module) - Viessmann Vitovalor PT2 E11T Installation And Service Instructions Manual

Table of Contents

Advertisement

Cleaning heating surfaces (gas condensing module)

!
Please note
Scratches to the surfaces of the heat exchanger
that come into contact with hot gas can result in
corrosion damage. Brushing can cause deposits
to become lodged in the gaps between the coils.
Never use brushes to clean the heating sur-
faces.
!
Please note
Prevent damage due to cleaning water.
Cover electronic components with suitable
watertight material.
Note
Discolouration on the heat exchanger surface is a nor-
mal sign of use. It has no bearing on the function and
service life of the heat exchanger.
The use of chemical cleaning agents is not required.

Checking condensate drain and cleaning the trap (gas condensing module)

1.
Fig. 65
3.
4.
Commissioning, inspection, maintenance
A
Fig. 64
1. Use a vacuum cleaner to remove combustion resi-
dues from heating surface
exchanger.
2. Flush heating surface
3. Check condensate drain. Clean the trap: See the
following chapter.
2.
A
of the heat
with water.
A
73