To correct phase order:
1. Turn off power to the unit, tag disconnect.
2. Reverse any two of the unit power leads.
3. Reapply power to the compressor, verify correct
pressures.
To verify the compressor is rotating in the proper
direction:
1. Connect service gages to the suction and liquid pres-
sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the liquid
pressure should rise, as is normal on any start- - up.
Compressor Overload —
This overload interrupts power to the compressor when
either the current or internal motor winding temperature
becomes excessive, and automatically resets when the
internal temperature drops to a safe level. This overload
may require up to 60 minutes (or longer) to reset. If the
internal overload is suspected of being open, disconnect
the electrical power to the unit and check the circuit
through the overload with an ohmmeter or continuity
tester.
Advanced Scroll Temperature Protection (ASTP) —
A label located above the terminal box identifies Copeland
Scroll compressor models that contain this technology. See
Fig. 16. Advanced Scroll Temperature Protection (ASTP) is
a form of internal discharge temperature protection, that
unloads the scroll compressor when the internal temperature
reaches approximately 149_C (300_F). At this temperature,
an internal bi- - metal disk valve opens and causes the scroll
elements to separate, which stops compression. Suction and
discharge pressures balance while the motor continues to
run. The longer the compressor runs unloaded, the longer it
must cool before the bi- - metal disk resets. See Fig. 17.
To manually reset ASTP, the compressor should be
stopped and allowed to cool. If the compressor is not
stopped, the motor will run until the motor protector trips,
which occurs up to 90 minutes later. Advanced Scroll
Temperature Protection will reset automatically before the
motor protector resets, which may take up to 2 hours.
Fig. 16 - - Advanced Scroll Temperature Protection Label
501 01 3600 01
*Times are approximate.
NOTE: Various factors, including high humidity, high ambient
Fig. 17 - - Recommended Minimum Cool-Down Time

Start Unit

Set the space thermostat to a set point above space
temperature so that there is no demand for cooling. Close
the CAS090 disconnect switch. Only the crankcase heater
will be energized.
Reset the space thermostat below ambient so that a call
for cooling is ensured.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Never charge liquid into the low-pressure side of
system. Do not overcharge. During charging or
removal of refrigerant, be sure indoor-fan system is
operating. Ensure both outdoor fan motors are
running; bypass any Motormaster function.
Adjust Refrigerant Charge —
Refer to Cooling Charging Chart, Fig. 18. For applications
with line lengths greater than 125 ft (38 m), contact your
service representative. Vary refrigerant until the conditions of
the chart are met. Note that the charging charts are different
from the type normally used. The charts are based on
charging the units to the correct subcooling for the various
operating
temperature sensing device are required. Connect the
pressure gage to the service port on the liquid line service
valve. Mount the temperature sensing device on the liquid
line close to the liquid line service valve, and insulate it so
that outdoor ambient temperature does not affect the reading.
Indoor airflow must be within the unit's normal operating
range. Operate the unit for a minimum of 15 minutes.
C10080
Ensure that pressure and temperature readings have
stabilized. Plot the liquid pressure and temperature on chart
and add or reduce the charge to meet the curve. Adjust the
charge to conform with the charging chart, using the liquid
pressure and temperature to read the chart.
Specifications are subject to change without notice.
120
110
100
90
80
70
60
50
40
30
20
10
0
0
10
20
30
40
50
Compressor Unloaded Run Time (Minutes)*
temperature, and the presence of a sound blanket will
increase cool-down times.
After Compressor is Stopped
CAUTION
!
conditions.
Accurate
60
70
80
90
C10081
pressure
gage
and
17