International comfort products CAS090 G Series Installation Instructions Manual page 12

R-410a split condensing units with rtpf coils
Table of Contents

Advertisement

4. Make sure the NFD shipped from the factory is at OFF
position (the arrow on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
6. Measure from the tip of the shaft to the top surface of
the black pointer; the measurement should be 3.75 - -
3.88 in. (95 - - 99 mm).
7. Tighten the locking screw to secure the shaft to the
NFD.
8. Turn the handle to the OFF position with red arrow
pointing at OFF.
9. Install the handle on to the painted cover horizontally
with the red arrow pointing to the left.
10. Secure the handle to the painted cover with (2) screws
and lock washers supplied.
11. Engaging the shaft into the handle socket, re- - install
(3) hex screws on the NFD enclosure.
12. Re- - install the unit front panel.
Fig. 11 - - Handle and Shaft Assembly for NFD
Units Without Factory-Installed
Non- - Fused Disconnect —
When installing units, provide a disconnect switch per NEC
(National Electrical Code) of adequate size. Disconnect
sizing data is provided on the unit informative plate. Locate
on unit cabinet or within sight of the unit per national or
local codes. Do not cover unit informative plate if mounting
the disconnect on the unit cabinet.
All Units —
All field wiring must comply with NEC and all local
codes. Size wire based on MCA (Minimum Circuit Amps)
on the unit informative plate. See Fig. 9 and the unit label
diagram for power wiring connections to the unit power
terminal blocks and equipment ground. Maximum wire
size is #2 ga AWG (copper only) per pole on contactors.
12
Provide a ground-fault and short-circuit over-current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over-current Protection) device size.
All field wiring must comply with the NEC and local
requirements.
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to
be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire with
the
and moving it to the 208-v
primary side of the transformer. Refer to unit label diagram
for line-side information. Field power wires will be
connected line- - side pressure lugs on the power terminal
block or at factory- - installed option non- - fused disconnect.
NOTE: Check all factory and field electrical connections
for tightness.
Affix the crankcase heater warning sticker to the unit
disconnect switch.
Voltage and Current Balance —
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Table 7. On 3-phase units, voltages between phases must
be balanced within 2% and the current within 10%. Use
the formula shown in the legend for Table 7, Note 4 (see
page 15) to determine the percent of voltage imbalance.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable warranty.
Convenience Outlets —
C12279
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag-out this switch, if necessary.
Non- - powered convenience outlets are offered on CAS090
models that provide a 125-volt GFCI (ground-fault
circuit-interrupter) duplex receptacle rated at 15-A behind
a hinged waterproof access cover, located on the end
panel of the unit. See Fig. 12.
Specifications are subject to change without notice.
-in. female spade connector from the 230-v connection
-in. male terminal on the
WARNING
!
501 01 3600 01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cas090 h series

Table of Contents