UNIT
V ---Ph---Hz
208/230--- 3--- 60
460--- 3--- 60
CAS090*G/H
575--- 3--- 60
Legend and Notes for Table 7
LEGEND:
FLA
---
Full Load Amps
LRA
---
Locked Rotor Amps
MOCP ---
Maximum Over Current
Protection
NEC
---
National Electrical Code
RLA
---
Rated Load Amps
}
Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and Fuse values are calculated in accordance with
The NEC. Article 440.
2. Motor RLA and LRA values are established in accordance
with Underwriters' Laboratories (UL). Standard 1995.
3. The 575--- v units are UL, Canada--- listed only.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
501 01 3600 01
Table 7 – Electrical Data — CAS090*G/H 60 Hz Units
WITHOUT POWERED CONVENIENCE OUTLET
VOLTAGE
COMPRESSOR
RANGE
}
MIN
MAX
RLA
LRA
187
253
24.0
186
414
506
12.6
100
518
633
9.9
78
Specifications are subject to change without notice.
POWER
OFM (ea)
SUPPLY
QTY
FLA
MCA
2
1.5
33
2
0.8
18
2
0.6
14
Example: Supply voltage is 230-3-60
max voltage deviation from average voltage
% Voltage Imbalance
= 100 x
AB = 224 v
BC = 231 v
AC = 226 v
(224 + 231 + 226)
Average Voltage =
3
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
DISCONNECT SIZE
MOCP
FLA
LRA
50
31
192
25
16
104
20
13
82
average voltage
681
=
3
4
227
15

Advertisement