Download Print this page

Specifications; General Specifications - Siemens Q Series T1 Instruction

Temperature sensors

Advertisement

Specifications

Operating range
Measurement range
Accuracy at room temperature (73F, 20C)
Environmental Conditions
Operation
Temperature (housing)
Humidity (housing)
Sensing element and Output signal
Time Constant
(QAP only without well)

General Specifications

Installation
Electrical Connections
Screw terminals for
Cable entry via
Grommet
Cable entry gland
Electrical Connections
Connecting cable
Cross-sectional area
Length
Dimensions
Housing
Probe
Minimum bending radius
Material Type
Base
Cover
Sensor sleeve
Connecting cables
Siemens Building Technologies, Inc.
Immersion
1 X (~16AWG) or (~14AWG) wire
1 X 2.5 mm² or X 1.5mm²
0.0085 - 0.0112 dia. cable
For 5.5 to 7.2 mm diameter cable
M 16 X 1.5
H
W
D
2.36" x 3.15" x 1.38"
(60mm x 80mm x 35mm)
4.0" (100mm)
N/A
Polycarbonate, RAL 7002
Polycarbonate, RAL 7035
N/A
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
Immersion
Duct
-40 to 158°F (-40 to 70C)
-22 to 266°F
(-30 to 130C)
+/-0.27F (+/-0.15C)
+/- 0.72F (+/-0.4C)
-40 to 158°F
5-95% RH
30s at 6.5 ft/s
N/A
H
W
2.36" x 3.15" x 1.38"
(60mm x 80mm x 35mm)
7.87" (200 mm)
0.4" (10mm)
Cable
-58 to 176°F
-22 to 266°F
(-50 to 80C)
(-30 to 130C)
+/- 0.72F (+/-0.4C)
-86 to 284°F
T1
30s at 6.5 ft/s
Duct
N/A
2-core, interchangeable
2 X .34 mm²
2.5M
D
L
8.2' x 0.24"
(2500mm x 6mm)
Stainless steel 1.4571
Printed in the U.S.A.
95%RH
2s
Cable
D
N/A
silicone
Page 2 of 3