Draining The Water; Refrigerant Piping Connection - Toshiba RAS-18J2KVRG-E Installation Manual

R32 or r410a inverter
Table of Contents

Advertisement

Draining the Water

Holes are provided on the base plate of the outdoor unit to ensure that the
defrost water produced during heating operations is drained off efficient.
If a centralized drain is required when installing the unit on a balcony or
wall, follow the steps below to drain off the water.
1. Proceed with water-proofing by installing the water-proof rubber caps
in the 2 elongated holes on the base plate of the outdoor unit. [How to
install the water-proof rubber caps]
1) Place four fingers into each cap, and insert the caps into the water
drain holes by pushing them into place from the underside of the base
plate.
2) Press down on the outer circumferences of the caps to ensure that
they have been inserted tightly.
(Water leaks may result if the caps have not been inserted properly, if
their outer circumferences lift up or the caps catch on or wedge against
something.)
Drain nipple
2. Install the drain nipple and a commercially available drain hose
(with 16 mm inside diameter), and drain off the water.
(For the position where the drain nipple is installed, refer to the
installation diagram of the indoor and outdoor units.)
• Check that the outdoor unit is horizontal, and route the drain hose at a
downward sloped angle while ensuring that it is connected tautly.
Base plate
Do not use ordinary garden hose, but one can flatten and prevent water
from draining.

Refrigerant Piping Connection

Flaring
1. Cut the pipe with a pipe cutter.
90
2. Insert a fl are nut into the pipe and fl are the pipe.
• Projection margin in fl aring : A (Unit : mm)
RIDGID (clutch type)
Outer dia.
of copper pipe
Ø6.35
Ø9.52
Ø12.70
Pipes thickness
Water-proof rubber caps
(supplied with the outdoor unit)
Base plate
Drain nipple
Commercially available
drain hose
Obliquity
Roughness
Conventional tool
Tool used
used
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0 to 0.5
1.0 to 1.5
0.8 mm or more
Die
Pipe
CAUTION
• Do not scratch the inner surface of the fared part when removing burrs.
• Flare processing under the condition of scratches on the inner surface of
fare processing part will cause refrigerant gas leak.
Tightening connection
Align the centers of the connecting pipes and tighten the fl are nut as far as pos-
sible with your fi ngers. Then tighten the nut with a spanner and torque wrench
as shown in the fi gure.
Externally
threaded side
Use a wrench to secure.
CAUTION
Do not apply excess torque. Otherwise, the nut may crack depending on
the conditions.
Outer dia. of copper pipe
Ø6.35 mm
Ø9.52 mm
Ø12.70 mm
• Tightening torque of fl are pipe connections
The operating pressure of R32 or
R410A is higher than that of R22
(approx. 1.6 times). It is therefore
necessary to fi rmly tighten the fl are
pipe connecting sections (which
connect the indoor and outdoor units)
up to the specifi ed tightening torque.
Incorrect connections may cause not
only a gas leakage, but also damage
to the refrigeration cycle.
Warp
10
IMPERIAL (wing nut type)
A
Outer dia. of copper pipe
Ø6.35
Ø9.52
Ø12.70
Pipes thickness
Half union
Flare nut
Use a torque wrench to tighten.
16 to 18 (1.6 to 1.8 kgf·m)
30 to 42 (3.0 to 4.2 kgf·m)
50 to 62 (5.0 to 6.2 kgf·m)
Tool used
1.5 to 2.0
1.5 to 2.0
2.0 to 2.5
0.8 mm or more
Internally
threaded side
(Unit : N·m)
Tightening torque
Flare at
indoor unit side
Flare at
outdoor unit side