Diagnostics Functions In The S5 Program Of The Master - Siemens IM 328–N Description

Sinumerik 805sm/840c link to sinec l2–dp
Table of Contents

Advertisement

Description
3.2 Description of the DP standard slaves
3.2.6
General notes on
diagnostics
3
Enabling
diagnostics
3-16

Diagnostics functions in the S5 program of the master

The STEP 5 program of the IM 328–B master can request and evaluate the
following diagnostics messages via the IM 328–N slave:
Diagnostics type
Diagnostics "Overview"
Diagnostics "Parameter as-
signment and addressability"
Station status
Device–related diagnostics
(stations diagnostics)
Identifier–related diagnostics
(module diagnostics)
n: Station number
Diagnostics "Overview" and "Parameter assignment and addressability"
are described in
Reference:
because they can be used on all slave stations.
The diagnostics function must first be enabled in the ET 200 SYSTEM PA-
RAMETER screen form (Y) and a diagnostics address must be specified (de-
fault diagnostics address: 252).
Diagnostics:
The diagnostics address is the address of the diagnostics word. The diagno-
stics data area of the master can be accessed with the diagnostics word. If an
error occurs, the slave stations send the diagnostics data to the master.
The two diagnostics bytes of the diagnostics word will be referred to as
DIAGNOSTICS ADDRESS (default: I/O byte 252) and DIAGNOSTICS
ADDRESS +1 (default: I/O byte 253).
By combining different diagnostics, appropriate conclusions can be drawn
such as, for example, station with fault and can be contacted.
Immediately after diagnostics is called in the STEP 5 program, the
diagnostics data are accessed and the diagnostics message is given in the
diagnostics word.
Request
127,0
Records all the stations for which
diagnostics data exist
126,n
Records all stations that can be para-
meterized and addressed
n,0
Provides information about the status
n,1
of the slave station
n,2
n,3
Provides information about the status
of the PLC in which slave IM 328–N
is slotted (PLC in RUN or in STOP?)
n,4
Not used by slave IM 328–N
/1/, SIMATIC S5 Distributed I/O System ET 200
Y
6ZB5 430–0BH02–1AA0
Siemens AG 1996 All Rights Reserved
Description
Diagnostics address: 252