Fans And Airflow; Fan Combinations; Power; Storing Components - Dell S6010-ON Installation Manual

Hide thumbs Also See for S6010-ON:
Table of Contents

Advertisement

Fans and airflow

The S6010–ON fans support two airflow options.

Fan combinations

Fans are installed as part of the factory install based on stock keeping unit (SKU) type. The system has SKUs that support the following
configurations:
AC or DC PSU with fan airflow from the I/O to the PSU
AC or DC PSU with fan airflow from the PSU to the I/O
Be sure to order the fans suitable to support your site's ventilation. Use a single type of airflow fan in your system.
NOTE:
Do not mix reverse and normal airflows in a single S6010-ON chassis.
For proper ventilation, position the system in an equipment rack (or cabinet) with a minimum of 5 inches (12.7 cm) of clearance around the
exhaust vents. When you install two systems near each other, position the two chassis at least 5 inches (12.7 cm) apart to permit proper
airflow. The fan speed increases when the internal temperature reaches 161.6°F (72°C) and decreases to normal speed when the
temperature falls to 136.4°F (58°C). The S6010-ON never intentionally turns off the fans.

Power

To connect the chassis to the applicable power source, use the appropriate power cord.
If the switch is an AC model, an country/region-specific AC power cord is included with the system.
If the switch is a DC model, a country/region-specific DC power cord is included with the DC power kit.
When installing AC systems, follow the requirements of the National Electrical Code, ANSI/NFPA 70 where applicable.
The system is powered-up when the power cord is connected between the system and the power source.
CAUTION:
Always disconnect the power cable before you service the power supply slots.
CAUTION:
Use the power supply cord as the main disconnect device on the AC system. Ensure that the socket-outlet is located/
installed near the equipment and is easily accessible.

Storing components

If you do not install your system and components immediately, properly store the system and all optional components following these
guidelines:
Storage location temperature must remain constant ranging from -40° to 158°F (from -40°C to 70°C)
Store on a dry surface or floor, away from direct sunlight, heat, and air conditioning ducts
Store in a dust-free environment
NOTE:
ESD damage can occur when components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the S6010–ON and its accessories. After you remove the original packaging, place the S6010–ON and its
components on an antistatic surface.
14
Site preparations

Advertisement

Table of Contents
loading

Table of Contents