The ANN-80 Series Remote Fire Annunciators and Indi-
cators (ANN-80, ANN-80-W, ANN-80C) are compact,
backlit LCD displays designed for use with compatible
FACPs Fire Alarm Control Panels. The displays mimic
the FACP display and are capable of displaying English-
language text of system point status including device type,
independent point alarm, trouble or supervisory zone and
custom alpha labels programmed into the FACP. Refer to
the FACP manual installation section for detailed system
information and wiring.
NOTE: Installation and wiring must be done in
accordance with NFPA 72 and local ordinances.

Specifications

TB1 Terminals 1 & 2
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and
nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble Condition: 39.0 mA
Alarm: 40.0 mA
AC Fail (not backlit): 15.0 mA
TB1 Terminals 3 & 4
ANN-BUS rated at 5.5 VDC and 60 mA max.
Dimensions
6 7/8"W x 5 3/8"H x 1 3/8"D
Mounting
The ANN-80 Series plastic enclosures can be surface or
semi-flush mounted in a single, double or 4" square elec-
trical box.
To mount the ANN-80 Series enclosure:
1.
Open the ANN-80 Series cover by turning the key
switch counterclockwise to the ON (Unlocked)
position.
2.
Push in the snap latch tab located on the right side
while pulling the cover open.
3.
Pull wire through 7/8" hole in backplate and feed
through wire channel to lower left corner of backplate
before routing to terminal block (refer to appropriate
FACP manual).
ANN-80 Series
Product Installation Document
PN 52749:D1 8/17/10 10-490
Cover with
LCD Display
Figure 1 Opening the ANN-80 Series
4.
The cover must remain attached to the backplate
while mounting the annunciator to the electrical box/
wall. The cover cannot be reattached or removed
after the annunciator has been mounted.
5.
If the cover should become detached from the
backplate, reattach as shown below.
ANN-80
ANN-80
Series
Cover
Backplate
Figure 2 Cover Reattachment
6.
Surface or Semi-flush mount the ANN-80 to a single,
double or 4" square electrical box. The
ANN-SB80KIT(-R/-B/-W) is an available kit that
contains two plastic backboxes that can be used to
surface mount the ANN-80 Series.
One Fire-Lite Place
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.firelite.com
Backplate
Press in latch
and then
Pull open cover
Key switch shown
in OFF position
• Position cover behind
backplate.
• Align hinge posts and
holes
Series
• Slide holes down
onto posts.
• Close cover to lock
hinges into place.
ANN-80
ANN-80
Series
Series
Cover
Backplate

Advertisement

loading

Summary of Contents for Honeywell Fire-Lite Alarms ANN-80 Series

  • Page 1: Specifications

    One Fire-Lite Place Northford, CT 06472-1653 USA 203-484-7161 • FAX 203-484-7118 www.firelite.com ANN-80 Series Product Installation Document PN 52749:D1 8/17/10 10-490 The ANN-80 Series Remote Fire Annunciators and Indi- Backplate cators (ANN-80, ANN-80-W, ANN-80C) are compact, backlit LCD displays designed for use with compatible FACPs Fire Alarm Control Panels.
  • Page 2: Setting The Dip Switches

    Wiring the ANN-80 Series to the FACP Setting the DIP Switches Refer to Table 1 and Figure 3 for wiring connections. Each ANN-BUS device requires a unique address. ANN-80 Series DIP switch S21 is used to set the address. This address will be displayed on the LCD display as the ANN-80 Series FACP ANN-BUS Station ID number.

This manual is also suitable for:

Fire-lite alarms ann-80-wFire-lite alarms ann-80c